To properly dissipate static electricity, the flooring system must be grounded with a copper grounding strap. Prior to installation, consult project electrician or electrical engineer regarding the placement of copper straps in order to synchronize copper strip placement with electrical grounding system location. Copper grounding straps must be placed every 2000 sq. ft., at least one per room. Prior to installing flooring materials, install copper straps directly into fresh adhesive and trowel adhesive over strap to fully embed strap in adhesive. Copper strap must be at least 18" in length, with at least 9" embedded into adhesive. The remaining copper material can be run up the wall for installation into electrical grounding system following flooring installation.